How To Operate The Fire Pump in The Fire Pump Room

Sep 19, 2025

The fire pump room is a very important part in fire use, and the duty personnel of the fire pump room should promptly notify the duty personnel of the fire control center in accordance with the regulations when using the fire pump. Now let's introduce the operating rules of the fire pump in the fire pump room.

The fire pump in the fire pump room is determined to operate in automatic start and manual stop modes.

1, The automatic (pressure switch controlled) startup process of the fire pump in the fire pump room:

Set the power switch control handle to the "ON" position in the distribution fire pump control cabinet of the fire pump room; When the pressure of the fire water pipe network is lower than 7.5kg/cm2, the fire pump in the fire pump room will automatically start supplying water; When it is below 5.5kg/cm2, the other fire pump in the fire pump room starts to supply water, and both fire pumps work simultaneously.

null

2, Steps for operating the "stop" of the fire pump in the fire pump room:

After selecting manual on the "automatic/manual" selection switch of the fire control panel in the fire control center, press the "stop" button of the fire pump in the fire pump room to stop the operation of the fire pump in the fire pump room, or press the "stop" button on the on-site electric fire pump control panel to stop the operation of the fire pump in the fire pump room.

3, Manual control and operation steps for the fire pump in the fire pump room:

Select 'Manual' on the 'Auto/Manual' selector switch on the fire control panel in the fire center; Set the power switch control handle to the "ON" position on the fire pump control box in the fire pump room; Press the "start" button on the fire control panel in the fire center to activate the fire pump in the fire pump room; Press the "stop" button on the fire control panel in the fire center to stop the fire pump in the fire pump room.

4, Local operation steps for the fire pump control box in the fire pump room:

Set the power switch control handle to the "ON" position in the fire pump control box of the fire pump room; Press the "Start" button on the fire pump control box in the fire pump room to activate the fire pump in the fire pump room; Press the "stop" button on the fire pump control box in the fire pump room to stop the fire pump in the fire pump room.